Short-circuit current of SPD disconnector is important 2025-11-27 16:30:56 The question of whether short-circuit current is an important factor in the regulations for disconnectors installed before surge protective devices (SPDs) can be clearly answered as “yes” for the following reasons: Regulatory and Technical Requirements The role of SPD disconnector This device safely disconnects the SPD from the system when it fails or requires maintenance. This disconnector can be installed either internally or externally (External SPD Disconnector). Short-circuit current and related standards According to representative KS C IEC 61643-11, KS C IEC 61643-12, and IEC 60364-5-53 regulations, SPD separators must have the ability to protect not only overcurrent (surge, fault, leakage, etc.) but also short-circuit current . In particular, the Disconnector installed before the SPD in the system must be able to withstand the **maximum short-circuit current (Isc)** that may flow through the SPD and circuit breaker, and must have the short-circuit withstanding rating (kA) specified by the SPD manufacturer or required by the relevant standards. Selection criteria for SPD disconnectors The rated short-circuit breaking current capacity (kA) of the separator , i.e. the capacity that can withstand a system short-circuit, must be taken into consideration, and this value must be determined by calculating the actual short-circuit current around the installation location of the SPD, etc. Typically, SPD external isolators are required to have the following ratings: thermal protection Over-current and short-circuit protection Surge impulse withstand Convenience of maintenance, etc. Real-world examples from standards/catalogs For external isolators specifically designed for SPDs used in practice, the “maximum short-circuit current (Isc)” rating is specified, and must be used in accordance with the system’s short-circuit current rating, such as 25kA . If the SPD Disconnector cannot withstand the short-circuit current of the system, serious secondary damage (fire, equipment damage, etc.) may occur to both the SPD and the system. Therefore, the short-circuit current rating must be considered and is required by regulations. conclusion In the regulations for disconnectors installed before surge protectors, “short-circuit current” is a very important factor and a key criterion that must be considered. That is, the separator must have a rating that can block/withstand more than the expected short-circuit current of the system, and this must be clearly stated in all domestic and international standards, design guidelines, and practice catalogs. The KS C IEC 61643-1 (IEC 61643-1) standard makes clear reference to short-circuit current in relation to the disconnector of SPD (surge protective device) . The standard stipulates that: It states that “the overloaded (short-circuited) SPD must be able to withstand the power short-circuit current that may occur in actual service”, and short-circuit current testing of the internal or external separator of the SPD is also required in actual testing. In the test, the voltage-limiting components of the SPD (e.g., MOV, circuit breaker, etc.) are replaced with a copper block (dummy) to evaluate whether the entire SPD (i.e., including the disconnector) normally disconnects at the maximum short-circuit current Isc specified by the manufacturer . At this time, the disconnector must function properly to safely disconnect the SPD from the system in a short-circuit current situation without fire, explosion, or damage. Therefore, short-circuit current (Isc) is an item that must be tested and required by regulations. These tests and evaluations are adopted not only in IEC 61643-1 but also in domestic KS C IEC 61643-1. Therefore, we can confirm that the short-circuit current related tests and safety requirements of SPD disconnectors are officially specified in KS C IEC 61643-1 . Short-circuit current is one of the most important safety requirements for SPDs (including disconnectors). LIST 이전글Damage from lightning strikes and surges of GIS in underground tunnels2025.11.27 다음글External abnormal voltages such as "lightning" and "surge" are defined in NFPC and NFTC 2025.11.27